Heat Exchanger LMTD Calculator

Find LMTD, the F correction and the heat transfer area you need.

Calculator

°C
°C

Enter the same value as the inlet for a condensing stream.

°C
°C

Enter the same value as the inlet for a boiling stream.

kW
W/m²K

Example Result

Your result will appear here

The calculated result will appear here after you press Calculate.

About the Heat Exchanger LMTD Calculator

The log mean temperature difference, or LMTD, is the true average driving force in a heat exchanger. Enter the four end temperatures and choose counterflow or parallel flow. Add a heat duty and a U value to get the area, and use the F correction for a multi-pass shell-and-tube unit. Leave inlet and outlet equal for a stream that condenses or boils.

How to Use the Heat Exchanger LMTD Calculator

  1. 1

    Choose counterflow, parallel flow or a 1-2 shell and tube.

  2. 2

    Enter the four end temperatures.

  3. 3

    For condensing or boiling, enter the same temperature for that stream's inlet and outlet.

  4. 4

    Add the heat duty and U to get the area.

  5. 5

    Press Calculate.

Heat Exchanger LMTD Calculator Examples

Frequently Asked Questions

How do you calculate LMTD?

LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂), using the temperature differences at each end.

What is a good LMTD?

There is no fixed target. A larger LMTD means less area, while a smaller one means closer temperatures and a bigger unit.

Is counterflow better than parallel flow?

Yes, unless one stream stays at a constant temperature, when they are equal.

What is the F correction factor?

A factor below 1 that adjusts LMTD for multi-pass and crossflow exchangers.

What is a temperature cross?

The cold outlet is hotter than the hot outlet. It is fine in true counterflow and a problem in single-shell multi-pass units.

Can I use LMTD for a condenser?

Yes. Enter the same temperature for hot in and hot out.

How do I find the area of a heat exchanger?

A = Q ÷ (U × F × LMTD).

By O.E. — Partner, chairman of the board and CEO of a metal products manufacturer for 21 years; the company exports to 45 countries.

Drafted with AI assistance; calculations checked against primary sources and tested with the site's own code. About FlowUtil

Last reviewed

LMTD with oil and water

Hot oil cools from 120 °C to 70 °C, heating water from 20 °C to 55 °C.

In counterflow the streams enter at opposite ends, so:

  • ΔT₁ = 120 − 55 = 65 °C
  • ΔT₂ = 70 − 20 = 50 °C
  • LMTD = (65 − 50) ÷ ln(65 ÷ 50) = 57.2 °C

In parallel flow both streams enter at the same end, so the differences are 100 °C and 15 °C, and LMTD = 44.8 °C.

Why not just take the average?

Temperature difference does not fall in a straight line along the exchanger. When the two end differences are close, the plain average is near enough: 57.5 °C against 57.2 °C. When they are far apart, it is not. In the parallel case the average of 100 and 15 is 57.5 °C, which overstates the true 44.8 °C by 28%. An exchanger sized that way would be 28% too small.

Turning LMTD into an area

Heat duty, area and LMTD are tied together: Q = U × A × LMTD.

So A = Q ÷ (U × LMTD). For a 500 kW duty and a U of 800 W/m²K:

ArrangementMean ΔTArea
Counterflow57.2 °C10.9 m²
1-2 shell and tube, F = 0.9051.6 °C12.1 m²
Parallel flow44.8 °C13.9 m²

The U value depends on the fluids, velocities and fouling, so take it from a test, a vendor or a proper thermal design. The duty comes from the flow: Q = ṁ × c_p × ΔT. Fluid speed drives U, and the Reynolds number calculator tells you whether the flow is turbulent. The guide to heat transfer covers the three modes.

Correcting a multi-pass exchanger

Most shell-and-tube units are neither pure counterflow nor pure parallel flow. Their mean difference is F × LMTD, using the counterflow LMTD. For one shell pass and two tube passes:

  • R = (T_h,in − T_h,out) ÷ (T_c,out − T_c,in)
  • P = (T_c,out − T_c,in) ÷ (T_h,in − T_c,in)
  • F = [S × ln((1 − P) ÷ (1 − P × R))] ÷ [(R − 1) × ln((2 − P × (R + 1 − S)) ÷ (2 − P × (R + 1 + S)))], with S = √(R² + 1)

For the oil and water case, R = 1.43, P = 0.35 and F = 0.90.

A common rule of thumb is to keep F at 0.75 or above. Below that, F falls steeply with small changes in temperature, so the design is unreliable. The usual fix is to add shells in series. Plate exchangers run close to true counterflow, and vendors publish their own factors.

Temperature cross: possible, but not in every exchanger

A cross means the cold stream leaves hotter than the hot stream leaves. In a true counterflow exchanger this is normal. In a 1-2 shell and tube, it costs dearly.

DutyCounterflow LMTD1-2 F
120→70, 20→55 (no cross)57.2 °C0.90
120→60, 30→70 (10 °C cross)39.2 °C0.62
120→60, 30→80 (20 °C cross)34.8 °CNot achievable

In parallel flow a cross cannot happen, since the two streams approach the same temperature. If the hot stream ever falls below the cold stream at the same point, the entered temperatures are impossible, and the calculator tells you so.

Condensers and boilers

When steam condenses at 120 °C and heats water from 20 °C to 55 °C, the hot side stays at one temperature. Enter 120 for both hot temperatures. The differences are 100 °C and 65 °C, and LMTD = 81.2 °C, whichever way the water flows. This is the one case where counterflow gives no advantage. F is 1 too, since the arrangement does not matter.

If both end differences are the same, the formula would give 0 ÷ 0, and the LMTD is simply that difference. This happens in counterflow when both streams have equal heat capacity rates: 100→50 °C against 30→80 °C gives 20 °C.

Working in Fahrenheit

LMTD is a temperature difference, so converting it is different from converting a temperature. Multiply by 1.8 and do not add 32. A result of 57.2 °C is a difference of 102.9 °F. Or enter all four temperatures in °F, and the result comes out in °F. The thermal conductivity converter handles related units, and heat duty in kW or BTU/h converts with the power converter.

Sources

  1. Tubular Exchanger Manufacturers Association, Standards of the TEMA, mean temperature difference charts.
  2. R. A. Bowman, A. C. Mueller and J. M. Nagle, Mean Temperature Difference in Design, Transactions of the ASME, 1940. https://doi.org/10.1115/1.4021450
  3. T. L. Bergman and others, Incropera's Fundamentals of Heat and Mass Transfer, Wiley.
  4. D. S. Kern, Process Heat Transfer, McGraw-Hill.